Power supply terminal for E-bus refresh, with diagnostics ELX9410
Run LED
Power E-bus LED
Power LED
+24 V
0 V
Top view 
extended temperature range

ELX9410 | Power supply terminal for E-bus refresh, with diagnostics

ExThe ELX9410 power supply terminal is used to refresh the E-bus. Data is exchanged between EtherCAT Coupler and EtherCAT Terminals over the E-bus. Each terminal draws a certain amount of current from the E-bus (see “current consumption E-bus” in the technical data). This current is fed into the E-bus by the corresponding coupler’s power supply unit. In configurations with a large number of terminals it is possible to use the ELX9410 in order to increase the E-bus power supply to 1 A. The ELX9410 has a diagnostics function, which is indicated by LEDs and on the process image.

In addition, the ELX9410 is equipped with a fin that can be used to check whether the separation distance stipulated by IEC 60079-11 is observed. This enables the installation of an additional ELX9560 power supply terminal in order to continue an ELX terminal strand on the same DIN rail. Moreover, two ELX9410 terminals can be installed in direct succession to reach the required separation distance for continuing the same terminal strand with standard EtherCAT Terminals. In this way, it is possible to conveniently combine the transmission of intrinsically safe signals with all features of the EtherCAT Terminals.

Technical data ELX9410
Technology power supply terminal
Short-circuit proof yes
Input voltage 24 V DC
Input current typ. 70 mA + (E-bus/4)
Output voltage 5 V for E-bus supply
Max. output current 1 A
Diagnostics in the process image yes
Special features E-bus refresh for ELX and EL terminals
Weight approx. 65 g
Housing width 12 mm
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos. IP 20/see documentation
Approvals/markings CE, UL, ATEX, IECEx, cFMus
Ex marking ATEX:
  II 3G Ex ec IIC T4 Gc
IECEx:
  Ex ec IIC T4 Gc
cFMus:
  Class I, Division 2, Groups A, B, C, D
  Class I, Zone 2, AEx nA IIC T4 Gc
  Class I, Zone 2, AEx ec IIC T4 Gc
further Ex components  
ELXxxxx EtherCAT Terminals with intrinsic safe in- and output
ELXxxxx-0090 EtherCAT Terminals with intrinsic safe in- and output and TwinSAFE SC
CPXxxxx Multi-touch Panel PCs and multi-touch Control Panels for use in hazardous areas, Zone 2/22